RECTIFIER MODULE

HTP I 48-1100

Beijing High-tech Dynamic Power
HTP I 48-1100 Rectifier Module

Introduction

HTP I 48-1100 is a digital rectifier with outstanding reliability, efficiency and power density. It is specially designed for telecom, network access and data center applications.

Features

  • High efficiency and high power density: 92% efficiency and 20.15W/in³ power density.
  • Digital control: Digital primary and secondary control, realize excellent monitoring and regulation.
  • High reliability design: One fan front-to-back airflow with latest thermal solution and experienced design.
  • Disconnect mains when hazardous input: HTP I 48/1100 will disconnect mains to protect itself when it can not sustain the input voltage.
  • Excellent EMC performance: Lower interference and excellent susceptibility give the module a better compatibility.
  • Global approvals: Meet CE, UL and TUV standard.
Input
Voltage 85-300VAC (Nominal: 220VAC)
Frequency 45-66Hz
Input Current <5.6Arms at 220VAC input, <6.9Arms at 176VAC input
Power Factor >0.99
THDi <5%
Output
Voltage 42-58V DC (Nominal 53.5V DC)
Power 1100W
Max. Current 21A at 53.5VDC
Static Voltage Regulation <0.6%
Dynamic Voltage Regulation <5% for 10%-90% load, regulation time < 50ms
Ripple <200mV peak to peak
Psophometric <2mV
Current Sharing <5%
Holdup Time >10ms
Startup Time 3-8s
Efficiency 92%

HTP I 48-1100 — RECTIFIER MODULE

Other Specifications
Operating Temp. -40 ℃ ~ 75 ℃
Storage Temp. -40 ℃ ~ 85 ℃
Relative Humidity <95% (non-condensing)
Altitude 4000m
IP Level IP20
Input Protection 6KA lightning protection
Output Protection 59±1Vdc Overvoltage shutdown; Short circuit proof; Output fuse
Isolation 3.0KVAC-input and output; 1.5KVAC-input and earth; 0.5KVAC-output and earth
Cooling One fan (front-to-back airflow)
Fan Speed Temperature and output current regulated
MTBF >300,000 hours (T_ambient: 25 ℃), Telcordia SR-332 Issue 1
Acoustic Noise ≤55dB at 220VAC input and full load (T_ambient < 30 ℃)
Dimensions 108W x 41.5 H x 208D (mm)
Weight 1.2Kg
Applicable Standards
Safety IEC60950-1, UL60950-1, EN60950-1
EMC EN55022 Class A (emission); IEC61000-3-2; IEC61000-3-3; IEC81000-4-2 (electrostatic discharge); IEC61000-4-3 (radiated immunity); IEC61000-4-4 (EFT); IEC61000-4-5 (surge immunity); IEC61000-4-6 (conducted immunity); IEC61000-4-8; IEC61000-4-11
Environment ETSI EN 300 019-2(-1,-2,-3); ETSI EN 300 132-2; Telcordia NEBS GR63 CORE Zone 4; RoHS compliant

Diagrams

HTP I 48-1100 Fig 1: output power vs. input voltage; Fig 2: output power vs. ambient temp.; Fig 3: output voltage vs. output current; Fig 4: efficiency vs. load (at 220VAC input)