HTP III 48-120AC-2000 is a digital inverter module. It is specially designed for telecom, network access and energy storage system applications and so on. It can work with outstanding reliability. HTP III 48-120AC-2000 supports parallel connection, and can also be used in 3-phase Y-type system.
Introduction
Features
- Digital control: Digital primary and secondary control, realizing excellent monitoring and regulation.
- High reliability design: One fan front-to-back airflow with latest thermal solution and experienced design.
- Excellent EMC performance: Lower interference and excellent susceptibility give the module better compatibility.
- Global approvals: Meets CE standards.
| DC Input | |
|---|---|
| Input Voltage Range | 42-58VDC (Nominal: 53.5VDC) |
| Maximum Input Current | 56A rms |
| Output | |
|---|---|
| Voltage | 90-140VAC (Nominal 120VAC) |
| Rated Current | 13.3A at 120VAC, resistive load |
| Frequency | 50/60Hz |
| Frequency Stability | ≤1% |
| Static Voltage Regulation | ≤1% |
| Dynamic Voltage Regulation | ≤10% (recovery time ≤60ms) |
| THDv | ≤3%, rated resistive load; ≤6%, rated non resistive load |
| Load Power Factor Requirement | ≥0.8 |
| Peak Efficiency | ≥92.6% |
| Current Sharing | ≤5% |
| Output Power | 2000VA/1600W (46-58VDC) |
| 50-58Vin Output Overload Capacity (Resistive load) | 105%≤Load≤125%, t≥10min; 125%<Load≤150%, t≥10S; Load>150%, t≤1S |
| 42-50Vin Output Overload Capacity (Resistive load) | 105%≤Load≤125%, t≥1min; Load>125%, t≤1S |
| Crest Factor | ≥3@140Vo/2000VA |