HTP III 48-220AC-3000 is a digital inverter module. It is specially designed for telecom, network access, energy storage systems, and similar applications. It can work with outstanding reliability, efficiency and high power density. HTP III 48-220AC/3000 supports parallel connection and can also be used in a 3-phase Y-type system (via monitor settings).
Introduction
Features
- Digital control: Digital primary and secondary control, realizing excellent monitoring and regulation.
- High reliability design: One fan front-to-back airflow with latest thermal solution and experienced design.
- Excellent EMC performance: Low emissions and excellent immunity provide better compatibility.
- Global approvals: Meets applicable CE standards.
| DC Input | |
|---|---|
| Input Voltage Range | 42-58VDC (Nominal: 53.5VDC) |
| Maximum Input Current | 75A |
| Output | |
|---|---|
| Voltage | 200-230VAC (Nominal 220/230VAC) |
| Rated Current | 10.9A at 220VAC, resistive load |
| Frequency | 50/60Hz |
| Frequency Stability | ≤1% |
| Static Voltage Regulation | ≤1% |
| Dynamic Voltage Regulation | ≤10% (recovery time ≤60ms) |
| THDv | ≤3%, rated resistive load; ≤6%, rated non-resistive load |
| Load Power Factor Requirement | ≥0.8 |
| Efficiency | ≥94% @53.5Vin/220Vo/50%load |
| Current Sharing | ≤5% |
| Rated Output Power | 3000VA/2400W (46-58VDC); 2500VA/2000W (other input) |
| 46-58Vin Output Overload Capacity (Resistive load) | 105%≤Load≤125%, t > 1min; Load > 125%, t≤1s |
| 42-46Vin Output Overload Capacity (Resistive load) | 105%≤Load≤125%, t > 10min; Load > 125%, t≤1s; 125% < Load≤150%, t > 10s |