RECTIFIER MODULE

HTP III 48-6000SE

Beijing High-tech Dynamic Power
HTP III 48-6000SE Rectifier Module

Introduction

HTP III 48-6000SE is a digital rectifier with outstanding reliability, efficiency and power density. It is specially designed for telecom, network access and data center applications.

Features

  • High efficiency and high power density: 97% efficiency and 25.5W/in³ power density.
  • Digital control: Digital primary and secondary control, realize excellent monitoring and regulation.
  • High reliability design: One fan front-to-back airflow with latest thermal solution and experienced design.
  • Excellent EMC performance: Lower interference and excellent susceptibility give module better compatibility.
  • Global approvals: Meet CE, UL and TUV standard.
Input
Voltage 208-530VAC(3phY) (Nominal 380VAC)
Frequency 45-66Hz
Input Current <13Arms at 305Vac input
Power Factor >0.99
THDi <5%
Output
Voltage 42-58V DC (Nominal 53.5V DC)
Power 6000W
Maximum Current 125A at 48VDC
Static Voltage Regulation <0.5%
Ripple <200mV peak to peak
Psophometric <2mV
Current Sharing <±5%
Hold up time >10ms
Startup time 3~8S
Efficiency 97%

HTP III 48-6000SE — RECTIFIER MODULE

Other Specifications
Operating Temp. -40 ℃ ~ 75 ℃
Storage Temp. -40 ℃ ~ 85 ℃
Relative Humidity <95% (non-condensing)
Altitude 2000m
IP Level IP20
Input Protection 5KA lightning protection
Output Protection 59.5±0.5Vdc Overvoltage shutdown; Short circuit proof; Output fuse
Isolation 4242VDC-input and output; 2121VDC-input and earth; 707VDC-output and earth
Cooling One fan (front to back airflow)
Fan Speed Temperature and output current regulated
MTBF >300000 hours (T_ambient: 25 ℃) Telcordia SR-332 Issue 1
Acoustic Noise ≤ 55dB at 220VAC input and full load (T_ambient: < 30 ℃)
Dimensions 108W x 86 H x 418D (mm)
Weight 5.0Kg
Applicable Standards
Safety IEC60950-1, UL60950-1, EN60950-1
EMC EN55022 ClassB(emission)
IEC61000-3-2, IEC61000-3-3
IEC61000-4-2(electrostatic discharge)
IEC61000-4-3(radiated immunity)
IEC61000-4-4(EFT)
IEC61000-4-5(surge immunity)
IEC61000-4-6(conducted immunity)
IEC61000-4-8, IEC61000-4-11
Environment ETSI EN 300 019 2(-1, 2, 3)
ETSI EN 300 132-2
Telcordia NEBS GR63 CORE Zone 4
RoHS compliant

Diagrams

HTP III 48-6000SE Fig 1: output power vs. input voltage; Fig 2: output power vs. ambient temp.
HTP III 48-6000SE Fig 3: output voltage vs. output current; Fig 4: efficiency vs. load at 380VAC input