DC/DC CONVERTER

HTPB48-48-5800

Beijing High-tech Dynamic Power
HTPB48-48-5800 DC/DC Converter

Introduction

HTPB48-48-5800 is a non-isolated DC/DC converter which has battery charging and discharging management function. It can automatically adapt to different charging voltages, with fast charging and long service life. Module can achieve the common use of batteries of different types, capacities, and manufacturers, adapting to the construction and maintenance needs of communication base stations.

Features

  • High efficiency and high power density: 96% efficiency and 25.5W/in³ power density.
  • Digital control: Digital primary and secondary control, realize excellent monitoring and regulation.
  • High reliability design: One fan front-to-back airflow with latest thermal solution and experienced design.
  • Excellent EMC performance: Lower interference and excellent susceptibility give the module a better compatibility.
  • Global approvals: Meet CE, UL and TUV standard.
Charging Mode
Bus Bar (Input)
Voltage range 43.2-58VDC
Rated voltage 53.5VDC
Input Current <105A at 57.6VDC input; <115A at 53VDC input
Battery (Output)
Voltage range 43.2-57.6VDC
Rated voltage 48VDC
Power 5760W
Max. Current 100A
Static Voltage Regulation < 0.5%
Ripple < 200mV peak to peak
Startup Time 3-8s
Efficiency 98%

HTPB48-48-5800 — DC/DC CONVERTER

Discharging Mode
Battery (Input)
Voltage range 43.2-57.6VDC
Rated voltage 48VDC
Input Current <105A at 58VDC input, <115A at 53VDC input
Bus Bar (Output)
Voltage range 43.2-58VDC
Rated voltage 53.5VDC
Power 5830W
Max. Current 110A at 53VDC
Static Voltage Regulation < 0.5%
Line Regulation < 0.1%
Load Regulation < 0.5%
Temperature Coefficient < 0.02%/ ℃
Dynamic Voltage Regulation < 5% for 10%-90% load, regulation time ≤50ms
Psophometric < 2mV
Ripple < 200mV peak to peak
Startup Time 3-8s
Efficiency 98%
Other Specifications
Operating Temp. -40 ℃ ~ 75 ℃
Storage Temp. -40 ℃ ~ 85 ℃
Relative Humidity < 95% (non-condensing)
Altitude 4000m
IP Level IP20
Input Protection 5kA lightning protection
Output Protection Overvoltage shutdown, short circuit protection, output fuse protection.
Isolation 707VDC-input and output to earth
Cooling One fan (front-to-back airflow)
Fan Speed Temperature and output current regulated
MTBF > 500000 hours (T_ambient: 25 ℃) Telcordia SR-332 Issue 1
Acoustic Noise ≤ 55dB at 48VDC input and full load (T_ambient: < 30 ℃)
Dimensions 107W x 40.8H x 270D (mm)
Weight 1.8Kg
Applicable Standards
Safety IEC60950-1, IEC60950-1, IEC60950-1
EMC EN55032 Class B (emission), IEC61000-3-2, IEC61000-3-3, IEC61000-4-2 (electrostatic discharge), IEC61000-4-3 (radiated immunity), IEC61000-4-4 (EFT), IEC61000-4-5 (surge immunity), IEC61000-4-6 (conducted immunity), IEC61000-4-8, IEC61000-4-11
Environment ETSI EN 300 019-2 (-1,-2,-3), ETSI EN 300 132-2

HTPB48-48-5800 — DC/DC CONVERTER

Diagrams (Charging Mode)

Diagrams (Charging Mode)

Diagrams (Discharging Mode)

Diagrams (Discharging Mode)