DC POWER SYSTEMS

HT SYS C2400200R48 Embedded Power System

Beijing High-tech Dynamic Power
HT SYS C2400200R48 Embedded Power System

Introduction

  • HT SYS C2400200R48 Embedded power system is a compact and intelligent power system, It can house up to 2*1.1KW rectifiers and 1*HT503 controller.
  • AC input, DC output and dry contact use front access and front operation.
  • With compact design, easy installation.
  • Two levels Low Voltage Disconnect (LVD) protection.
  • Two fuses for battery.
  • Compatible with rectifiers of the same size.

Applications

  • Fiber optic network
  • Access network
  • Satellite communication ground station
  • Transmission equipment
  • Mobile communication
  • ESS (Energy Storage System)

Features

  • 19" 1U sub-rack, easy to be embedded into all standard telecom equipment.
  • Up to 2.2kW system capacity.
  • Up to 0.99 power factor.
  • Intelligent fan-cooling.
  • Rectifier modules hot-swap.
  • N+1 rectifier module redundancy.
  • Advanced batteries monitoring and management.
  • ECO mode.
  • High power density.

Applicable Standards

Applicable Standards
Electrical IEC 60950-1, EN 60950-1, UL 60950-1
EMC EN 55022 Class A

HT SYS C2400200R48 Embedded Power System — DC POWER SYSTEMS

Input
AC Input 80Vac-300Vac
Input Current ≤6.9A (Per rectifier)
Frequency 45~65Hz
THDi <5%@full load, <10%@half load, Rated input and output voltage
Output
Output Voltage -53.5V Rated output voltage
Output Current -53.5V float voltage, -56.4V boost voltage, ≥40A
Voltage Regulation ≤±1%
Current Sharing ≤±5%
Efficiency ≥91%
Ripple and Noise ≤200mV Peak-Peak
Psophometric Noise ≤2mV
Other Specifications
Operating Temperature -40°C to +70°C (-40°F to +158°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity Operating: ≤95% non-condensing; Storage: ≤99% non-condensing
Dimensions (mm) 482.6W (19") x 44H (1U) x 279.5D
Weight ≤5kg (Without rectifier)
Protection Level IP 20
Options
DC Distribution 5*10A/1P+2*20A/1P fuses for load, 2 fuse for battery, the rating of load fuse is 20A, BLVD & LLVD1 (Optional), Front operation and front connection
AC Distribution AC input mode: 1*IEC C14 socket, Front access and Front connection
Low Voltage Disconnect 80A Bi-stable contactors should be used as BLVD
Output Protection Short-circuit protection, Overload protection
Rectifier HTP I 48-1100
Monitoring
Function Operation information acquirements, battery and system management, system alarm, communicate with control center related ports
Controller HT503
Dry Contact 2 relay outputs, NO+COM
Digital Input 2 DI
Interface LCD
Temp Sensor 2