DC POWER SYSTEMS

5U Embedded Power System

Beijing High-tech Dynamic Power
5U Embedded Power System

Introduction

  • It is a compact and intelligent power system. It can house up to 4×4 kW or 4×3 kW rectifiers and 1×HT505 controller.
  • AC input, DC output and dry contact are all front-access and front-operated.
  • With micro-compact design for easy installation.
  • Two-level Low Voltage Disconnection (LVD) protection.
  • Four-branch battery MCBs.
  • Compatible with rectifiers of the same size.

Features

  • 5U subrack, easily to be embedded into any standard 19" rack or 335mm deep rack
  • Up to 16kW system capacity
  • Up to 0.99 power factor
  • Intelligent fan-cooling
  • Rectifier modules hot-swap
  • Advanced batteries monitoring and management
  • ECO mode
  • High power density

Applications

  • Fiber optic network
  • Access network
  • Satellite communication ground station
  • Transmission equipment
  • Mobile communication
  • ESS
  • 5G base station/Micro base station

Applicable Standards

Applicable Standards
Electrical IEC 62368-1, EN 62368-1, UL 62368-1
EMC EN 55032
Environmental ETSI EN 300019-2, ETSI EN 300132-2, RoHS

5U Embedded Power System — DC POWER SYSTEMS

Input
Input Voltage 85-300VAC (Nominal: 220VAC)
Input Current ≤26A (Per 4kW rectifier) or ≤19A (Per 3kW rectifier)
Frequency 45-65Hz
THDi <5%@full load; <10%@half load; Rated input and output voltage
Output
Output Voltage 53.5V (43.2--58Vdc adjustable)
Output Current ≤600A@53.5V
Static Voltage Regulation ≤0.5%
Current Sharing ≤5%
Efficiency ≥97% (4kW rectifier); ≥96% (3kW rectifier)
Ripple and Noise ≤200mV Peak-Peak
Psophometric Noise ≤2mV
Other Specifications
Operation Temperature -40°C to +75°C (-40°F to +167°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity Operation: ≤90% non-condensing; Storage: ≤95% non-condensing
Dimensions (mm) 482.6W (19") x 221.5H (5U) x 335D
Weight ≤25kg (without rectifier)
Options
Model HT016D048B01
AC Input AC MCBs: 1×63A/4P; AC SPD board: Class C (In=20kA @8/20μs); Front operation and front connection
Rectifier 4*HTP III 48-4000HE or 4*HTP III 48-3000HE
DC Output 16kW Max.
DC Distribution BLVD Load MCBs: 2*125A/1P1+8*up to 63A/1P; LLVD Load MCBs: 2*125A/1P1+7*up to 63A/1P; Battery MCBs: 2*125A/1P; DC SPD board: Class C (In=10kA @8/20μs); Front operation and front connection
LVD level Two levels of 200A bi-stable contactors
Output Protection Short-circuit protection, Overload protection
Monitoring
Function Operation information acquirements, battery and system management, system alarm, communicate with control center related ports
Controller HT505
Battery Mid-Point 2 x Battery mid-point
Dry Contact 6 relay outputs
Digital Input 6 DI
Interface LCD