Get Quote

RECTIFIER MODULE

HTP III 48-6000HE

Beijing High-tech Dynamic Power
HTP III 48-6000HE Rectifier Module

Introduction

HTP III 48-6000HE is a digital rectifier with outstanding reliability, efficiency and power density. It is specially designed for telecom, network access and data center applications.

Features

  • High efficiency and high power density: 96% efficiency with excellent power density.
  • Digital control: Digital primary and secondary control, realizing excellent monitoring and regulation.
  • High reliability design: One fan front-to-back airflow with latest thermal solution and experienced design.
  • Excellent EMC performance: Lower interference and excellent susceptibility give the module a better compatibility.
  • Global approvals: Meet CE, UL and TUV standard.
Input
Voltage 208~530VAC(3phY) (Nominal 380VAC)
Frequency 45-66Hz
Input Current <12Arms at 305Vac input
Power Factor >0.99
THDi <5%
Output
Voltage 43.2~58V DC (Nominal 53.5V DC)
Power 6000W
Maximum Current 125A at 48VDC
Static Voltage Regulation ±0.5%
Dynamic Voltage Regulation <5% for 10%~90% load, regulation time < 50ms
Ripple <200mV peak to peak
Psophometric <2mV
Current Sharing <±5%
Hold up Time >10ms
Startup Time 3-8s
Efficiency 96%

HTP III 48-6000HE — RECTIFIER MODULE

Other Specifications
Operating Temp. -40℃ ~ 75℃
Storage Temp. -40℃ ~ 85℃
Relative Humidity <95% (non-condensing)
Altitude 2000m
IP Level IP20
Input Protection 5KA lightning protection
Output Protection 59.5±0.5Vdc Overvoltage shutdown; Short circuit proof; Output fuse
Isolation 3.0KVAC-input and output; 1.5KVAC-input and earth; 0.5KVAC-output and earth
Cooling One fan (front-to-back airflow)
Fan Speed Temperature and output current regulated
MTBF >300,000 hours (T_ambient: 25℃), Telcordia SR-332 Issue 1
Acoustic Noise ≤ 55dB at 220VAC input and full load (T_ambient: < 30℃)
Dimensions 108W x 86 H x 418D (mm)
Weight 4.4Kg
Applicable Standards
Safety IEC60950-1, UL60950-1, EN60950-1
EMC EN55022 Class B (emission)
IEC61000-3-2, IEC61000-3-3
IEC61000-4-2 (electrostatic discharge)
IEC61000-4-3 (radiated immunity)
IEC61000-4-4 (EFT)
IEC61000-4-5 (surge immunity)
IEC61000-4-6 (conducted immunity)
IEC61000-4-8, IEC61000-4-11
Environment ETSI EN 300 019-2(-1,-2,-3)
ETSI EN 300 132-2
Telcordia NEBS GR63 CORE Zone 4
RoHS compliant

Diagrams

HTP III 48-6000HE Fig 1: output power vs. input voltage; Fig 2: output power vs. ambient temp.
HTP III 48-6000HE Fig 3: output voltage vs. output current; Fig 4: efficiency vs. load at 380VAC input