Get Quote

DC POWER SYSTEMS

3U Embedded Power System

Beijing High-tech Dynamic Power
3U Embedded Power System

Introduction

  • It is a compact and intelligent power system, It can house up to 3*3kW rectifiers and 1*HT505 controller
  • AC input, DC output and dry contact use front access and front operation
  • With micro-compact design, easy installation
  • Two levels Low Voltage Disconnect (LVD) protection
  • Two branchs battery MCBs
  • Compatible with rectifiers of the same size

Applications

  • Fiber optic network
  • Access network
  • Satellite communication ground station
  • Transmission equipment
  • Mobile communication
  • ESS
  • 5G base station/Micro base station

Features

  • 3U subrack, easily to be embedded into any standard 19" rack or 342mm deep rack
  • Up to 9kW system capacity
  • Up to 0.99 power factor
  • Intelligent fan-cooling
  • Rectifier modules hot-swap
  • Advanced batteries monitoring and management
  • ECO mode
  • High power density

Applicable Standards

Applicable Standards
Electrical IEC 62368-1 EN 62368-1
UL 62368-1
EMC EN 55032
Environmental ETSI EN 300 019-2
ETSI EN 300 132-2
RoHS

3U Embedded Power System — DC POWER SYSTEMS

Input
Input Voltage 85-300VAC (Nominal: 220VAC)
Input Current ≤19A (Per 3000W rectifier)
Frequency 45~65Hz
THDi <5%@full load; <10%@half load; Rated input and output voltage
Output
Output Voltage 53.5V (43.2~58Vdc adjustable)
Output Current ≤168A@53.5V
Static Voltage Regulation ≤0.5%
Current Sharing ≤5%
Efficiency ≥96%
Ripple and Noise ≤200mV Peak-Peak
Psophometric Noise ≤2mV
Other Specifications
Operating Temperature -40°C to +70°C (-40°F to +167°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity Operating: ≤90% non-condensing; Storage: ≤95% non-condensing
Dimensions (mm) 482.6W (19") x 132H (3U) x 342D
Weight ≤15kg (without rectifier)
Options
Output Socket HT009D048A02
AC Input AC MCBs: 1*D63A/2P; AC SPD: Class C (In = 20kA@8/20μS);
Rectifier 3*HTP III 48-3000HE
DC Output 9kW Max
DC Distribution BLVD Load MCBs: 163A + 232A + 116A
LLVD Load MCBs: 163A + 232A + 116A
Battery MCBs: 2*100A
DC SPD board: Class C (In = 10kA@8/20μS)
Front operation and front connection
Low Voltage Disconnect level Two level of 125A Bi-stable contactor
Output Protection Short-circuit protection, Overload protection
Monitoring
Function Operation information acquirements, battery and system management, system alarm, communicate with control center related ports
Controller HT505
Battery Mid-Point 2 x Battery mid-point
Dry Contact 6 relay outputs
Digital Input 6 DI
Interface LCD
Temp Sensor 2