Get Quote

DC POWER SYSTEMS

HT SYS E1800200R48 Embedded Power System

Beijing High-tech Dynamic Power
HT SYS E1800200R48 Embedded Power System

Introduction

  • HT SYS E1800200R48 system is a compact and intelligent power system, It can house up to 4*1.1KW rectifiers and 1*HT503 controller
  • DC output and dry contact use front access and front operation, AC input use rear connection
  • With compact design, easy installation
  • Two levels Low Voltage Disconnect (LVD) protection
  • Two battery MCBs
  • Compatible with rectifiers of the same size

Features

  • 19"2U sub-rack, easy to be embedded into all standard telecom equipment
  • Up to 4.4kW system capacity
  • Up to 0.99 power factor
  • Intelligent fan-cooling
  • Rectifier modules hot-swap
  • N+1 rectifier module redundancy
  • Advanced batteries monitoring and management
  • ECO mode
  • High power density

Applications

  • Fiber optic network
  • Access network
  • Satellite communication ground station
  • Transmission equipment
  • Mobile communication
  • ESS (Energy Storage System)

Applicable Standards

Applicable Standards
Electrical IEC 60950-1, EN 60950-1, UL 60950-1
EMC EN 55022 Class A

HT SYS E1800200R48 Embedded Power System — DC POWER SYSTEMS

Input
AC Input 80Vac-300Vac
Input Current ≤6.9A (Per rectifier)
Frequency 45~65Hz
THDi <5%@full load; <10%@half load; Rated input and output voltage
Output
Output Voltage -53.5V Rated output voltage
Output Current -53.5V float voltage; -56.4V boost voltage; ≥80A
Voltage Regulation ≤±1%
Current Sharing ≤±5%
Efficiency ≥91%
Ripple and Noise ≤200mV Peak-Peak
Psophometric Noise ≤2mV
Other Specifications
Operating Temperature -40°C to +70°C (-40°F to +158°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity Operating: ≤95% non-condensing; Storage: ≤99% non-condensing
Dimensions (mm) 482.6W (19") x 88.1H (2U) x 265D
Weight ≤10kg (Without rectifier)
Options
DC Distribution LLVD: 2*25A/1P + 2*5A/1P; BLVD: 4*1A/1P; 2 MCBs for battery, the rating of load MCB is 12A; BLVD & LLVD1; Front operation and front connection
AC Distribution AC Input mode: Terminal Block; Rear access and rear connection
Low Voltage Disconnect 80A Bi-stable contactors should be used as LLVD1 & BLVD
Output Protection Short-circuit protection; Overload protection
Rectifier HTP I 48-1100
Monitoring
Function Operation information acquirements, battery and system management, system alarm, communicate with control center related ports
Controller HT503
Dry Contact 6 relay outputs, NO+COM
Digital Input 6 DI
Interface LCD
Temp Sensor 2