Get Quote

DC POWER SYSTEMS

HT SYS E2201500R48S02 Embedded Power System

Beijing High-tech Dynamic Power
HT SYS E2201500R48S02 Embedded Power System

Introduction

  • HT SYS E2201500R48S02 system is a compact and intelligent power system, It can house up to 4x3KW rectifiers and HT503 or HT505 controller.
  • Dry contact use front access and front operation. AC input and DC output use rear access and rear connection.
  • With compact design, easy installation.
  • Compatible with rectifiers of the same size.
  • Three levels Low Voltage Disconnect (LVD) protection.

Applications

  • Fiber optic network
  • Access network
  • Satellite communication ground station
  • Transmission equipment
  • Mobile communication
  • ESS (Energy Storage System)

Features

  • 19"2U sub-rack, easy to be embedded into all standard telecom equipment
  • Up to 12KW system capacity
  • Up to 0.99 power factor
  • Intelligent fan-cooling
  • Rectifier modules hot-swap
  • N+1 rectifier module redundancy
  • Advanced batteries monitoring and management
  • ECO mode
  • High power density

Applicable Standards

Applicable Standards
Electrical IEC 60950-1 EN 60950-1, UL 60950-1
EMC EN55022 ClassB(emission)
Environmental ETSI EN 300 019-2, ETSI EN 300 132-2, RoHS

HT SYS E2201500R48S02 Embedded Power System — DC POWER SYSTEMS

Input
AC Input Tolerance: 85-300 Vac; Nominal: 176-300 Vac
Input Current ≤15Arms at 220VAC Input; ≤19Arms at 176VAC Input
Frequency 45~65Hz
THDi <5%@full load; <10%@half load; Rated input and output voltage
Output
Output Voltage -53.5V Rated output voltage
Output Current -53.5V float voltage; -56.4V boost voltage; ≤200A
Voltage Regulation ≤±1%
Current Sharing ≤±5%
Efficiency ≥95.5%
Ripple and Noise ≤200mV Peak-Peak
Psophometric Noise ≤2mV
Other Specifications
Operating Temperature -40℃ to +70℃ (-40℉ to +158℉)
Storage Temperature -40℃ to +85℃ (-40℉ to +185℉)
Humidity Operating: ≤95% non-condensing; Storage: ≤99% non-condensing
Dimensions(mm) 482.6W x 88.1H x 395D
Weight ≤10kg (Without rectifier)
Options
DC Distribution LVD/(200A): Connect to the busbar by M8 screws. The positive connect by M8 screws. The negative of the battery connect to the busbar by M8 screws. BLVD & LLVD1&LLVD2; Rear operation and rear connection
AC Distribution Connect to backplane directly; Rear access and rear connection
Low Voltage Disconnect 200A Bi-stable contactors should be used as BLVD & LLVD1&LLVD2
Output Protection Short-circuit protection Overload protection
Rectifier HT Power II 48 3000HE
THDi <5%@full load; <10%@half load; Rated input and output voltage
Monitoring
Function Operation information acquirements, battery and system management, system alarm, communicate with control center related ports
Controller HT503 / HT505
Dry Contact 6 relay outputs, NO+COM
Digital Input 6 DI
Interface LCD
Temp Sensor 2
Battery Mid-Point 4 x Battery mid-point