Get Quote

DC POWER SYSTEMS

HT SYS EA301750R48S03

Beijing High-tech Dynamic Power
HT SYS EA301750R48S03 DC Power System

Introduction

  • It is a compact and intelligent power system. It can house up to 4*3KW rectifiers and 1*HT505 controller.
  • AC input and DC output are connected on the back, dry contact use front access and front operation.
  • With micro-compact design, easy installation.
  • Three levels Low Voltage Disconnect (LVD) protection.
  • Compatible with rectifiers of the same size.

Applications

  • Fiber optic network
  • Access network
  • Satellite communication ground station
  • Transmission equipment
  • Mobile communication
  • ESS
  • 5G base station/Micro base station

Features

  • 2U subrack, easily to be embedded into any standard 19" rack or 347mm deep rack.
  • Up to 12kW system capacity.
  • Up to 0.99 power factor.
  • Intelligent fan-cooling.
  • Rectifier modules hot-swap.
  • Advanced batteries monitoring and management.
  • ECO mode.
  • High power density.

Applicable Standards

Applicable Standards
Electrical IEC 62368-1, EN 62368-1, UL 62368-1
EMC EN 55032
Environmental ETSI EN 300 019-2, ETSI EN 300 132-2, RoHS

HT SYS EA301750R48S03 — DC POWER SYSTEMS

Input
Input Voltage 85-300VAC (Nominal: 220VAC)
Input Current ≤19A (Per 3000w rectifier)
Frequency 45~66Hz
THDi <5%@full load, <10%@half load, Rated input and output voltage
Output
Output Voltage 53.5V (43.2~58Vdc adjustable)
Output Current ≤224.3A@53.5V
Static Voltage Regulation ≤0.5%
Current Sharing ≤5%
Efficiency ≥96.3%
Ripple and Noise ≤200mV Peak-Peak
Psophometric Noise ≤2mV
Other Specifications
Operating Temperature -40°C to +75°C (-40°F to +167°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity Operation: ≤90% non-condensing; Storage: ≤95% non-condensing
Dimensions (mm) 482.6W (19") x 88.6H (2U) x 347D
Weight ≤10kg (without rectifier)
Options
Subrack Model HT SYS EA301750R48S03
AC Input Terminal blocks (Located on the rear PCB board)
Rectifier 4*HTP III 48-3000HE
DC Output 12kW Max.
DC Distribution BLVD/Priority load (200A): Connect to the busbar of rear side.
LLVD1/Non-Priority load (200A): Connect to the busbar of rear side.
LLVD2/Non-Priority load (200A): Connect to the busbar of rear side.
Low Voltage Disconnect level Three level of 200A Bi-stable contactors
Output Protection Short-circuit protection, Overload protection
Monitoring
Function Operation information acquirements, battery and system management, system alarm, communicate with control center related ports
Controller HT505
Battery Mid-Point 4
Dry Contact 12
Digital Input 12
Interface LCD
Temp Sensor 4